Реле безопасности серии MSR138DP (Guard master)

Цена: 0 грн

Description

The MSR138DP can be connected in 3 different input wiring configurations: 1 normally closed, 2 normally closed, or 2 OSSD. When connected in the two normally closed fashion, the MSR138DP checks for cross faults across the two inputs. When connected to light curtains, the light curtain must perform the cross-fault detection.

The MSR138DP has output monitoring that can accommodate either automatic/manual reset or a monitored manual reset. When configured with automatic/manual reset (jumpers on X1-X2 and X3-X4), the MSR138DP can have the reset terminals S33-S34 jumpered or can be converted to an unmonitored manual reset by adding a normally open switch in the monitoring loop (S33-S34). When configured to monitored manual reset, the MSR138DP checks the output monitoring circuit through the manual application of the reset switch. The unit cannot be reset until the timing function has completed.

The outputs of the MSR138DP include two normally open immediate safety outputs and three normally open delayed safety outputs. The outputs of the MSR138.1DP include two normally open immediate safety rated outputs, two normally open delayed safety outputs and one normally closed delayed safety output. The safety outputs have independent and redundant internal contacts to support the safety function. If a reset request is made during the time cycle, it will cause a lockout condition. Cycle inputs after timing has completed and reset after the delay time has expired to clear lockout. Connecting contacts 55-56 of the MSR138.1DP in series to Y1-Y2 can avoid this lockout.

A normally closed timer reset switch can be added to force the delayed contacts open prior to the completion of the timing cycle.


Features
 

  • Category 4/3 per EN 954-1
  • Stop category 0 and 1
  • Light curtain, E-stop, safety gate inputs
  • Two immediate safety outputs
  • Delayed outputs: 3 N.O. safety or 2 N.C. safety and 1 N.C. aux.
  • Cross fault monitoring
  • Monitored or automatic reset
  • Removable terminals


LED Indicators
 

Green Power—Illuminates when power on
Green Start—Illuminates when S33-S34 is closed
Green CH1 IN—Illuminates when channel 1 input is closed
Green CH2 IN—Illuminates when channel 2 input is closed
Green CH1—Illuminates when K1 is closed
Green CH2—Illuminates when K2 is closed
Green CHT1—Illuminates during timing period
Green CHT2—Illuminates during timing period
  


Specifications
 

Safety Ratings
Standards EN 954-1, ISO 13849-1, IEC/EN 60204-1, IEC 60947-4-1, IEC 60947-5-1, ANSI B11.19, AS4024.1
Safety Classification Cat. 4 per EN 954-1 (ISO 13849-1), SIL CL3 per EN IEC 62061, PLe per ISO 13849-1
Functional Safety Data ⋆ 
Note: For up-to-date information, visithttp://www.ab.com/safety/
PFHD: < 2.38 x 10-9
MTTFd: > 195 years
Suitable for performance levels Ple (according to ISO 13849-1:2006) and for use in SIL3 systems (according to IEC 62061) depending on the architecture and application characteristics
Certifications CE Marked for all applicable directives, cULus, c-Tick, and TÜV
Power Supply
Input Power Entry 24V AC/DC, 115V AC or 230V AC
Power Consumption 4 W
Inputs
Safety Inputs 1 N.C., 2 N.C. or LC
Input Simultaneity Infinite
Input Resistance, Max. 135 W
Reset Auto./Manual or Monitored Manual
Power On Delay/
Recovery Time
1 second/100 ms
Response Time 15 ms
Outputs
Safety Contacts 2 N.O.
Auxiliary Contacts Delayed 3/2 N.O.
Thermal CurrentIlth 5 x 2.5 A or 3 x 3.5 A nonswitching
Rated Impulse withstand Voltage 2500V
Switching Current @ Voltage, Min. 10 mA @ 10V
Fuses, Output External 6 A slow blow or 10 A fast acting
Electrical Life (Operations) (With surge suppression)
250V AC/6 A/1500VA cosf = 1…0.1 M
250V AC/2.5 A/625VA cosf = 1…0.5 M
250V AC/1.5 A/375VA cosf = 0.35…0.3 M
250V AC/5 A/1250VA cosf = 0.6…0.1 M
24V DC/2 A/48 W = 1 M
10V DC/0.01 A/0.1 W = 2 M
Mechanical Life 2,000,000 cycles
Utilization Category
Resistive: AC-1 7 A@ 250V AC  
Resistive: DC-1 7 A/24V DC  
Inductive: AC-15 6 A@ 250V AC 6 A @ 125V AC
Inductive: DC-13 3 A/24V DC 6 A/24V DC @ 6 ops/min
UL B300, 5 A/250V AC, 24V DC
Environmental and Physical Characteristics
Enclosure Type Rating/
Terminal Protection
IP40 (NEMA 1)/
IP20
Operating Temperature [C (F)] -5…+55 ° (23…131 °)
Vibration 10…55 Hz, 0.35 mm
Shock 10 g, 16 ms, 100 shocks
Mounting 35 mm DIN Rail
Weight [g (lb)] 24V DC: 350 (0.77); 115/230V AC: 490 (1.08)
Conductor Size, Max. 0.2…4 mm2 (24…12 AWG)
 
⋆ Usable for ISO 13849-1:2006 and IEC 62061. Data is based on the following assumptions:
- Mission time/Proof test interval of 20 years
- Functional test at least once within six-month period


Product Selection
 

Inputs Safety Outputs Delayed Safety Outputs Delayed Auxiliary Outputs Time Delay Terminals Reset Type Power Supply Cat. No.
1 N.C., 2 N.C., Light Curtain 2 N.O.⋆  3 N.O.‡ 
(MSR138DP)
1.0 seconds, fixed Removable Auto./Manual or Monitored Manual 115V AC 440R-M23080
0.15…3 s 24V AC/DC 440R-M23143
Spring Clamp 440R-M23143S
0.15…3 seconds Removable 115V AC 440R-M23141
230V AC 440R-M23140
0.5…10 s 24V AC/DC 440R-M23147
Spring Clamp 440R-M23147S
0.5…10 seconds Removable 115V AC 440R-M23145
230V AC 440R-M23144
1.5…30 seconds 24V AC/DC 440R-M23151
115V AC 440R-M23149
230V AC 440R-M23148
2 N.O.‡ 
(MSR138.1DP)
1 N.C. 0.15…3 seconds 24V AC/DC 440R-M23084
115V AC 440R-M23082
230V AC 440R-M23081
0.5…10 seconds 24V AC/DC 440R-M23088
115V AC 440R-M23086
230V AC 440R-M23085
1.5…30 seconds 24V AC/DC 440R-M23092
115V AC 440R-M23090
230V AC 440R-M23089
  
⋆ Instantaneous safety outputs Cat. 4
‡ Delayed safety outputs are Cat. 3


Accessories
 

Description Cat. No.
Bag of 4, 4-Pin Screw Terminal Blocks 440R-A23209
Bag of 4, 4-Pin Spring Clamp Terminal Blocks 440R-A23228
  


Approximate Dimensions

Dimensions are shown in mm (in.). Dimensions are not intended to be used for installation purposes.
 

Click to enlarge - 440R-M23080-151_Dim


Block Diagram
 

Компания Hydronix – мировой лидер в сфере производства микроволнового оборудования для измерения влажности сыпучих материалов, бетонных смесей и пр.
Датчики Hydronix заслужили непревзойденную репутацию благодаря точности измерений, прочности конструкции и эксплуатационной надежности. Функциональная гибкость изделий Hydronix позволяет эффективно интегрировать их в любую...

ООО «Интеравтоматика» является официальным партнером международного концерна OEM Automatic. OEM Automatic - фирма, более сорока лет специализирующаяся на производстве и поставках компонентов промышленной автоматики и электроники, имеющая филиалы в двенадцати европейских странах. Акции OEM Automatic котируются на Стокгольмской фондовой бирже.

ООО «Интеравтоматика» является официальным дистрибьюторм фирмы Jay Electronique. Компания Jay Electronique  является производителем устройств управления и передачи информации, основанных на использовании беспроводной связи. Jay Electronique специализируется на  следующих направлениях деятельности:
микроволновая передача данных;
работа с различными...

Mafelec - производитель элементов контроля и управления топ-уровня. Ассортимент продукции исключительного качества составляют: Специальные кнопки для транспортных средств, автобусов, аэропортов, поездов, железных дорог, кнопки для панелей управления водителей, специальные индикаторные лампы.
Дисплеи для сообщений, информационные дисплеи (для вокзалов, аэропортов), иллюминационные...

 
Адрес: 49126, г. Днепропетровск, ул. Паникахи, 2

Тел./факс:

+38 (056) 744-97-31, +38 (056) 795-00-89
+38 (067) 618-05-10, +38 (050) 405-47-58

E-mail: info@interautomatic.com.ua